DTMS is the best temperature monitoring solution for where distributed, long-range temperature monitoring is required
This equipment can measure the temperature up to ~20km distance
Product design
①
DTMS
ESS system battery overheats monitoring
Substations overheat monitoring
Factory facility overheat monitoring
Power line overheat monitoring
Power plant facility overheat monitoring
Water, Gas leakage monitoring
①
④
⑦
③
⑥
⑨
⑤
⑧
②
Status indicator(power/network/error)
②
Optical output channels (1~8)
⑤
USB port
③
HDMI for Monitor
④
Ethernet port
RS-232 port
⑥
RS-485 port
⑦
H/W interface for alarm
⑧
Power connector
⑨
Specifications
Channel
Termination Type
Connector Type
Optical Fiber
Laser Wavelength
Measurement Range
Sampling Resolution
Spatial Resolution
Temperature Resolution
Temperature Tolerance
Measurement Time
Measurement Temperature range
Measurement Type
Status Monitoring
Communication Interface
Monitor Interface
Power Consumption
Input Power
Size (H x W x D)
Weight BICOM DTMS Specification
1 ~ 8 Channel
Opened
SC/APC
62.5um Multi Mode
1550nm
~ 5Km, ~ 10Km, ~20Km
0.1m
1.5m
~ 0.3 ℃
± 1 ℃
~ 1sec/Ch.
-40 ℃ ~ + 160 ℃
Fixed and Differential
Optical Fiber, Network, Device failure
Ethernet, TCP/IP, USB, Modbus
HDMI
20W(Typ.)
100 ~ 240V AC 50,60Hz
19’ Rack (88 x 483 x 384)
15Kg Application Design
ESS Batteries
DTMS
DTMS
Bank #1
Bank #2
Bank #3
Bank
Network
The Internet
Cloud Server
Remote Monitoring
Network
The system is configured in such a way that one DTMS device is connected per bank.
■
Each DTMS device transmits the measured temperature data to the cloud server through Ethernet.
Each DTMS device transmits the measured temperature data to the cloud server through Ethernet.
The temperature data stored in the cloud server is monitored remotely through the network through an analysis and visualization process.
Water/Gas Leakage
10°C
0°C
1km
2km
3km
4km
5km
6km
↙
Leakage Point
Network
Remote
Monitoring Cloud Server
The Internet
Network
Fiber Optic Cable
DTMS Device #1
DTMS Device #2
DTMS Device #3
Fiber Optic Cable
Pipeline #1
Pipeline #2
Pipeline #3
■
■
■
Industrial Applications
DTMS